System Control and Data Aquistion
Peak Environmental Monitoring can provide specialist System Control And Data Acquisition (SCADA) and/or Data Acquisition (DAQ) to extend the functionality of existing telemetry hardware.
Projects include but not limited to

water management

environmental monitoring

energy and mining sectors
SCADA project example - Shannon Creek Dam ( 2010)

undertaken by Dr Robyn Hannah consultant for Peak Environmental Monitoring


see also Shannon Creek Dam - Coffs Harbour Council

The 30,000 megalitre Shannon Creek Dam is located west of Coutts Crossing and 18 kilometres south of Grafton on the NSW north coast. It is an off-river storage reservoir. This means that instead of relying on rain to fall in the small 37km catchment area of the Shannon dam for its water supply, water is gravity fed by pipes directly from the Nymboida river. The Nymboida river sources its water from 1700 square km of Dorrigo catchment, the highest rainfall area in NSW.
SCADA Technical details

650 physical points

300 calculated or derived points. Including measurements of rainfall, stream height and flow, reservoir level, pump and inlet flow, motor speeds, power, energy usage, stop/start functions, valve operation and flow, reservoir temperature profile.

One of the major computations was a reservoir balance which ensured that all natural flow into the reservoir was discharged to keep downstream environment unchanged. This was based on base level monitoring of the site and an algorithm determined from it.

One main PLC but it was distributed over 50 locations, connected by cable and optical fibre.

Outlying PLC’s measured environmental parameters and telemetered these back to the control centre using Trio radio systems.
* Oil pipeline project undertaken by
Dr Robyn Hannah
B.E. PhD ( Hons 1 )
[Home] [Products-Adcon] [Products-Environmental] [Products-Water] [Products-Soil Moisture] [Products- Sentek] [Products - Irrigation]
[Services - SCADA] [References] [FAQ] [About] [Site Map]
PEAK ENVIRONMENTAL MONITORING
... data aquisition and control systems
email:- info@peakmonitoring.com.au